top of page

PowerManager

Intelligent Power Control –  Mission-Ready

Commercial power system inverter engineered for austere environments. Preconfigured and plug-and-play, it integrates grid, generator, and solar inputs to deliver efficient and resilient power conversion.

Image_edited.png
Image_edited.png
Image_edited.png

Output: 1.25 MW and 2.5 MW 

DC Input : 511–1500 VDC

AC Input: 800 VAC Grid/Gen/DER

UL Certified: 1741 Ed. 3 

Image_edited_edited.png
f90d2c32-b2b7-4706-9453-5ccc69f64a7b_edi
Icon-Shipping Container.png

Protections: Multiple built-in
Optimized: Three-level topology
Ingress: NEMA 3R/IP 54
Warranty: 10 Years

Certifications
UL 1741 Ed. 3, IEEE 1547, CSA 22.2 #107.1, IEEE 519, and CEC listed

1.25 MW PowerManager

PHYSICAL DIMENSIONS

  • Parameter: CPS-1250 Specification

  • Module Dimensions: 80 in x 49 in x 44 in 

  • Weight: 1,980 lbs (898 kg)

 

ELECTRICAL SPECIFICATIONS

  • AC Input Voltage: 800, 690, 660, 630, 600, 540, 480, 415, 350 VAC

  • Grid Frequency: 60 Hz

  • Maximum Apparent Power: 1336 kVA (@800VAC) down to 585 kVA (@350VAC)

  • Maximum Real Power: 1336 kVA (@800VAC) down to 585 kVA (@350VAC)

  • Maximum AC Current: 964 ARMS

  • DC Voltage Range: 511-1500 VDC (@350-800 VAC)

  • Maximum DC Current: 1170 ADC

  • Power Factor: Four Quadrant

  • Maximum Efficiency: 98.5% (@1500 VDC), 98.7% (@1280 VDC)

 

THERMAL PARAMETERS & PROTECTION

  • Operating Temperature: -30°C to +60°C, De-rated above +45°C 

  • Cooling: Forced Air Cooled 

  • Enclosure: NEMA 3R/IP 54 

  • AC Breaker: Shunt Trip 

  • Battery Protection: Voltage and Current Curtailment 

  • Anti-Islanding Protection: Open Phase at Inverter Terminals 

  • Voltage & Frequency Fault Protection: DC/AC Over/Under Voltage, Frequency, Current Faults 

  • DC Input Protection: DC Input Fuses, DC Pre-Charge 

  • Surge Protection: AC Surge Protection 

SYSTEM

  • Cooling: Forced Air Cooled 

  • Enclosure: NEMA 3R/IP 54 

  • Temperature Monitoring & Power Curtailment: Included 

PowerManager Front and Back.png

2.5 MW PowerManager

THERMAL PARAMETERS

  • Parameter: CPS-2500 Specification

  • Module Dimensions: 80 in x 85 in x 44 in

  • Weight: 3,970 lbs(1,800 kg)

 

ELECTRICAL SPECIFICATIONS

  • AC Input Voltage: 800, 690, 660, 630, 600, 540, 480, 415, 350 VAC

  • Grid Frequency: 60 Hz

  • Maximum Apparent Power: 2672 kVA (@800VAC) down to 1169 kVA (@350VAC)

  • Maximum Real Power: 2672 kW (@800VAC) down to 1169 kW (@350VAC)

  • Maximum AC Current: 1928 ARMS

  • DC Voltage Range: 511-1500 VDC (@350-800 VAC)

  • Maximum DC Current: 2340 ADC

  • Power Factor: Four Quadrant

  • Maximum Efficiency: 98.5% (@1500 VDC), 98.7% (@1280 VDC)

 

THERMAL PARAMETERS & PROTECTION

  • Operating Temperature: -30°C to +60°C, De-rated above +45°C 

  • Cooling: Forced Air Cooled 

  • Enclosure: NEMA 3R/IP 54 

  • AC Breaker: Shunt Trip 

  • Battery Protection: Voltage and Current Curtailment 

  • Anti-Islanding Protection: Open Phase at Inverter Terminals 

  • Voltage & Frequency Fault Protection: DC/AC Over/Under Voltage, Frequency, Current Faults 

  • DC Input Protection: DC Input Fuses, DC Pre-Charge 

  • Surge Protection: AC Surge Protection 

SYSTEM

  • Cooling: Forced Air Cooled 

  • Enclosure: NEMA 3R/IP 54 

  • Temperature Monitoring & Power Curtailment: Included 